buildwiz.uk

Wall Ties: Types, Spacing, Embedment, What Building Control Checks

UK homeowner guide to cavity wall ties: choosing the type and length, spacing, minimum embedment, installation checks and repairs to older walls.

By Ian

Project managed a £182k Oxfordshire kitchen extension

A wall tie is a small connector, but a wall with missing or poorly installed ties can become unstable. Your building control officer may inspect the ties while the cavity is still visible. Agree the inspection stages before work starts, and make sure the bricklayer knows when to leave work exposed. Tie selection, spacing and embedment need checking as the wall rises, not after the cavity has been closed.

What a wall tie does

A cavity wall has two separate walls, called leaves or skins, with a gap between them. A typical extension has an outer brick leaf and an inner block leaf, with insulation and sometimes a clear air space in the cavity. The leaves are not bonded together by the brickwork itself. Without suitable restraint, the outer leaf can bow or pull away under wind loading.

Wall ties connect the leaves. Each end is bedded into a mortar joint as the wall rises, allowing lateral forces to pass between the two skins. The ties help the wall work as designed; they are not a substitute for the rest of the structural design, including support at floors and roofs.

Missing ties are a structural defect even when the finished brickwork looks tidy. Once the wall is closed, the position and embedment of the ties are difficult to inspect. Photographs taken during construction can help record the work, but they do not replace the checks agreed with building control.

New-build ties are installed in fresh mortar as the bricklayer works up the wall. They must not simply be pushed into a joint that has already been built. Adding ties to a completed wall requires a designed remedial system and suitable installation tools.

Choosing the right type of wall tie

For masonry-to-masonry walls, BS EN 845-1 is the product standard and PD 6697 describes the familiar duty classifications, Types 1 to 4. The appropriate type depends on the building and its location. Height alone is not enough: wind exposure, altitude, cavity width and the particular product all matter.

Ask the designer or structural engineer to specify the tie, then order that product in the correct length. The table below explains the broad categories. It is not a substitute for checking the manufacturer's limits for your site.

TypeDuty / example productUse it whenLimits
Type 1Heavy duty (e.g. Ancon ST1)Tall buildings, parapets, exposed or coastal sites, wide cavities up to 225mm in one pieceCheck the product limits and structural specification
Type 2General purpose (e.g. Ancon RT2)Most low and mid-rise housing on normal sitesProduct and site limits apply; commonly specified up to 15m
Type 3BasicLighter housing applicationsCheck the permitted height, wind exposure and cavity width
Type 4Light duty (e.g. Ancon HRT4)Low-rise houses and most single and two-storey extensions on sheltered sitesTypically houses up to 10m; verify exposure and the product cavity range

A Type 4 housing tie may suit a sheltered low-rise extension, but do not change the specification by guessing that a heavier tie will solve every problem. Check any substitution with the designer. A wider cavity can require a different product, even if the building is only one storey high.

Older butterfly ties are not a useful default for a new order. Choose a current product with the required performance declaration. Separating walls also have sound-transmission requirements under Approved Document E; a tie suitable for an external wall is not automatically suitable for every party-wall detail.

Correct tie installation: drip pointing down and centred, 50mm minimum embedment each end, cavity kept clear of mortar.

Materials and corrosion in older walls

Austenitic stainless steel is the usual choice for new masonry cavity walls. The specification should state the suitable material and product for the exposure conditions. Specialist low-conductivity ties are also available, but substituting one requires the designer to check its structural and thermal performance. Do not assume that any metal tie found at a merchant is suitable for an external cavity wall.

Older houses may contain galvanised steel ties. If their protective coating deteriorates, the steel can corrode. Rust occupies more space than the original metal and can force the surrounding mortar joints apart. The age of a house is a reason to investigate, not proof that its ties have failed.

Horizontal cracks at repeated bed-joint levels can be a sign of tie corrosion. Bulging brickwork is another reason to seek an assessment. Neither symptom identifies the cause on its own: movement, support problems and other defects can also damage masonry. A survey needs to establish the wall construction and condition of the ties.

Warning

If a survey flags possible wall-tie failure, ask what evidence supports the finding. Confirm that the affected wall has a cavity and request photographs or inspection results. An independent structural engineer or suitably experienced surveyor can assess whether repairs are needed before you accept a replacement contractor's quote.

Matching tie length to cavity width

The tie must embed properly into both leaves. Use the cavity width and the product's required embedment to select its length. Approved Document A Table 5 gives the following sizes for the masonry construction within its scope. These are the familiar stock sizes, not permission to use any tie of that length.

Cavity widthTie lengthTypical use
50-75mm200mmOlder or narrow cavities
76-100mm225mmCommon traditional cavity
101-125mm250mmMost modern extensions
126-150mm275mmWider cavity with thicker insulation
151-175mm300mmWide cavity, partial-fill insulation
Over 175mmCavity width + 125mmEngineer-reviewed; round up to next stock length

For a 150mm cavity, the table calls for a 275mm tie. If it is centred, that leaves 62.5mm at each end. A 250mm tie would leave only 50mm at each end, with no allowance for an uneven cavity or an off-centre tie. This is why ordering from the table matters.

For cavities wider than 175mm, start with the cavity width plus 125mm and select a suitable stock length in accordance with the manufacturer's guidance. A 200mm cavity gives a calculated length of 325mm. Products requiring deeper embedment need extra length. Confirm the tie's approved cavity range as well as its overall length.

Spacing and layout

For the usual masonry cavity wall with both leaves at least 90mm thick, the general minimum density is 2.5 per m². The standard grid has maximum spacings of 900mm horizontally and 450mm vertically. Follow the design if it calls for closer spacing.

Arrange the ties in a staggered pattern across the wall. Marking the positions helps the bricklayer maintain the spacing as work progresses. Counting a few visible ties is not enough: check their distribution across the whole panel and the additional ties at its edges.

Openings and unrestrained edges need extra restraint. The usual detail places additional ties within 225mm of the edge, at no more than 300mm vertical centres. Check window and door reveals, roof verges and movement-joint details against the design; do not continue the ordinary wall grid past an opening without adding its edge ties.

Coordinate the first tie course with the damp proof course and the insulation layout. Follow the specified detail rather than placing ties wherever the next convenient joint happens to fall.

Standard tie grid and edge-tie rule: staggered diamond pattern at 900 x 450mm, with extra ties within 225mm of every reveal at 300mm vertical centres.

Drip orientation and embedment depth

The position of each tie matters as much as the number installed. Check the following details while both ends and the cavity are still visible.

First, check the drip. Where the tie has a central drip, it should normally face down and sit in the middle of the cavity. This lets water fall away instead of tracking along the tie to the inner leaf. Follow the product instructions for any different drip arrangement.

Second, check the slope. The tie should be level or fall slightly towards the outer leaf. A tie sloping towards the inner leaf can carry water inwards and contribute to penetrating damp.

Third, keep the cavity clean. Mortar droppings can lodge on ties and form a bridge across the gap. Remove them as work proceeds; access becomes much harder once more courses have been built. Do not bend or cut a tie to make it fit unless the manufacturer permits that adjustment.

Then embedment. Each tie must be bedded a minimum depth into each leaf: Approved Document A and NHBC both set the minimum at 50mm per leaf. Tie makers design for 62.5mm in each leaf so that at least the minimum ends up bedded after site tolerances.

Warning

Approved Document A, NHBC and LABC all give 50mm as the minimum embedment in each leaf, and some proprietary ties need more, so follow the tie maker's instructions and the tie lengths in Approved Document A. Check the tie length against your cavity width before the bricklayer starts: ties too short for the cavity leave shallow embedment and require an agreed remedial solution.

Retaining clips for partial-fill insulation

If your cavity uses partial-fill insulation batts, compatible retaining clips hold the boards against the inner leaf. Loose boards can leave gaps in the insulation or obstruct the remaining clear cavity. Order the clips with the ties and check that they fit the specified product.

Follow the insulation manufacturer's fixing pattern, including the support required at board edges and in the first row. Do not assume that the ordinary structural tie grid provides every fixing an insulation board needs. The residual cavity must also match the approved insulation system and wall design. Check these details before the boards hide the inner ends of the ties.

What building control checks

Agree the inspection stages with building control before construction starts. The following checklist helps you check the visible work before an inspection. There is no single inspection schedule that applies to every project, so confirm which stages must remain exposed and when work can continue.

CheckWhat good looks like
Spacing900mm horizontal, 450mm vertical maximum, staggered
DensityAt least 2.5 ties per square metre across the panel
Edge tiesExtra ties within 225mm of openings and reveals at 300mm vertical centres
MaterialSpecified stainless steel or approved specialist product confirmed
EmbedmentAt least 50mm per leaf (more if the tie maker specifies it)
DripFacing down and centred in the cavity
SlopeLevel or sloping toward the outer leaf; inward slope fails
Cavity cleanlinessNo mortar snots on ties; clips present if partial-fill

An inspection can only assess the work visible at the time. Later courses still need the same care, and an inspection does not transfer responsibility for workmanship away from the builder. Keep checking cavity cleanliness and tie placement as the wall rises.

Remedial ties in older houses

Failed ties do not always mean that the whole wall has to be rebuilt. Specialist contractors can install remedial ties through drilled holes in existing masonry. Whether this is suitable depends on the condition of both leaves, the mortar and any movement that has already occurred. A bulging or unstable wall needs a structural assessment before a repair method is chosen.

Remedial systems include mechanical, helical and resin-bonded ties. Some helical systems use an SDS drill with a dedicated setting tool; other systems rely on anchors or resin in prepared holes. Their installation methods are not interchangeable. The contractor should specify the product, its suitability for the actual masonry and the checks needed to confirm a sound fixing.

The repair specification must also address the existing ties. Corroding ties may need isolation or removal so that further expansion does not keep damaging the wall. Ask how the contractor will deal with them and what testing or records will demonstrate that the replacement ties are secure.

A free survey offered by a company selling replacement work is also a sales assessment. Ask for evidence of the defect, a written scope and comparable quotes. An independent assessment is useful where the diagnosis is uncertain or the proposed work is extensive. Comparing only the number of new ties can miss differences in access, testing and treatment of the old ties.

Cost and where to buy

A box of 250 stainless steel ties typically costs £36 – £90. Compare the same type, length and pack size when checking prices. A cheaper box is no saving if the ties are too short or unsuitable for the specified cavity.

Builders' merchants and specialist fixing suppliers stock common lengths. Give the supplier the product reference and length from the specification, and include any compatible retaining clips in the order. Check availability before the bricklayer reaches the relevant courses. Keep the packaging or delivery record so the installed product can be identified.

Remedial work is a different purchase from a box of new-build ties. Its cost depends on access, the extent of the defect, the selected system and treatment of the original ties. Ask whether scaffolding, testing, making good and VAT are included. A written scope makes quotes comparable and helps prevent extra charges for work that was assumed to be included.

External resource

LABC: Installing cavity wall ties in masonry walls

Local Authority Building Control guidance on spacing, embedment (at least 50mm into each leaf), material, drip orientation, and slope.

labc.co.uk

External resource

Approved Document A: Structure

Structural guidance for England. Table 5 gives cavity widths, tie lengths and minimum embedment; check the applicable guidance for other UK nations.

gov.uk

External resource

Ancon: Wall tie spacing and lengths

Manufacturer guidance on selecting tie length, allowing for site tolerances and placing ties around openings.

ancon.co.uk

Where to buy Wall tie

Check current prices from UK suppliers.

These are affiliate links: if you buy through them we may earn a small commission, at no extra cost to you. Learn more.

Common mistakes

Too few ties. Measure the grid and check the additional ties at edges. A handful of correctly placed ties does not prove that the whole wall meets the specified density.

Wrong tie length for the cavity. A 150mm cavity normally takes a 275mm tie under the table above. A 250mm tie leaves only the bare minimum embedment if perfectly centred. Check the actual cavity and the product requirements before ordering.

Ties sloping inward or drips pointing up. Check orientation while the tie is visible. Water should be directed away from the inner leaf, following the manufacturer's installation detail.

Mortar bridging the cavity. Remove droppings as the wall rises. Leaving them on ties can create a path for moisture across the cavity.

Skipping extra ties at openings. Check each reveal and the specified movement-joint detail. The general wall grid does not provide the extra restraint required at every edge.

Unapproved substitutions. A different tie type or material needs the designer's agreement. Match the delivered product to the specification before it is bedded into the wall.

Where you'll need this

Wall ties are installed during the structure stage of a masonry cavity-wall build. These related tasks explain how the work fits together:

Keep the tie specification, delivery details and construction photographs with your project records.

Where this fits in your build

This is one step in a bigger build. Pick up the sequence around it.

Snagging ChecklistSystematically inspect every element of the finished extension and compile a snagging list for the builder to rectify before final payment.Damp Proof CourseInstall the damp proof course (DPC) and damp proof membrane (DPM) to prevent moisture rising into the new structure.Building Control NotificationSubmit a building regulations application to the local authority or a registered building control approver before construction begins.The Standard Building Control FollowsA foundational reference map explaining the three-layer regulatory framework that building control enforces: the Building Regulations 2010 (the legal duty), the Approved Documents A-T and AD 7 (how to comply), and the BS/EN/NHBC technical standards beneath them (the precise numbers). Covers all current Approved Documents with their scope and relevance to a typical extension, the October 2023 dutyholder regime, and how to navigate to the specific document when a BCO cites a particular Part.What Building Control Inspects at Each StageDetailed paid guide covering exactly what the BCO looks for at each inspection stage: lintels over openings, wall ties at correct centres, cavity trays, DPC positioning, drainage falls and air tests, insulation certificates, electrical test certificates. Helps homeowners understand what to expect and why being informed protects them from builders cutting corners.Getting Quotes and ComparingObtain at least three detailed, like-for-like quotes from builders and evaluate them on price, specification, and reliability signals.Walls and BlockworkBuild the extension walls using cavity wall construction with facing brick outer leaf and insulated block inner leaf.Building Control Inspection: StructureArrange the building control inspection at superstructure stage to verify wall construction, steel placement, and damp proofing.

Pricing up this job?

The Block and Mortar Estimator gives you a quick estimate for this part of the work. Free, no email needed.

Open the calculator

Budgeting the whole extension? Get the free spreadsheet with every cost category and contingency worked out, or follow the full step-by-step guide with the Access Pass.

More in this category

Related reference pages

Weep ventSmall plastic insert placed in the perpend (vertical mortar joint) below a cavity tray to allow water that has entered the cavity to drain back outside. Required at maximum 900mm centres per Approved Document C.Building SandFine, smooth sand used for mortar mixes in bricklaying and blockwork. Produces a workable, cohesive mortar that adheres well to masonry units.Cavity boardA strip of timber, foam, or polystyrene dragged up through the cavity as brickwork courses are laid, catching mortar droppings that would otherwise land on the DPC or wall ties and bridge the cavity. Removed and cleaned at intervals during bricklaying.Cavity closerPrefabricated insulated frames installed at window and door openings to close the cavity and prevent thermal bridging. They help meet Parts C (moisture) and L (thermal) of the Building Regulations; the 0.45 m²K/W minimum thermal resistance comes from the Accredited Construction Details, not Part L itself, and in a masonry house wall Approved Document B (Diagram 5.3) asks only that the cavity is closed around openings, with no fire rating for the closer. First-fix installation during wall construction is required by NHBC/LABC standards.Cavity trayPreformed angles and straights made from pitch-polymer or CPT, installed at abutments where the extension roof meets the existing house wall to direct cavity moisture back outside through weep vents.Concrete Blocks 100mm (Lightweight/Aerated)Lightweight aerated concrete blocks (e.g. Thermalite, Celcon) used for inner leaf of cavity walls. Better thermal performance than dense blocks and easier to cut and handle.

General guidance for homeowners in England (and Wales where we say so), not professional advice. Every site is different: check anything that affects your build with a qualified professional, your local council or building control. Terms