buildwiz.uk

Drain Test Kit: Pre-Test Your Drainage Before the Building Inspector Arrives

What an air test kit is, the BS EN 1610 / Approved Document H test method, and why a low-cost kit pays for itself by catching leaks before the BCO visit.

By Ian

Project managed a £182k Oxfordshire kitchen extension

The drainage inspection turns on an air test, and an air test is binary: the pressure holds for the prescribed time or it doesn't. Fail it with the BCO standing over the trench and the sequence that follows is fixed: the run exposed, every joint checked, the leak found and resealed, a re-inspection booked, days lost, and the groundworker's payment milestone stuck behind the retest. Running the same test yourself the day before, with a kit that costs less than the delay, is how the real inspection becomes a formality.

A 40 pound drain test kit, used the day before the BCO visit, catches a leak while the trench is still open and the groundworker is still on site. The kit is the single highest-value tool a homeowner can buy for an extension build, and almost no homeowner project plans include it.

What a drain test kit is

A drain test kit is a small bag of equipment that lets you perform a pressure test on a section of drainage pipe before it's signed off by Building Control. The components are simple: a 110mm drain bung (the standard UK soil pipe diameter), a flexible hose, a small hand pump, and a pressure gauge or U-tube manometer.

You seal the ends of the test section with bungs, then use the pump to raise the air pressure inside the pipe to a specified level. The gauge reads the pressure. After a settling period you watch the gauge for the specified test period (seven minutes for the Approved Document H air test). If the pressure drops more than the allowed amount, the pipe has a leak somewhere along the test length.

The kit is a one-off purchase under 50 pounds from Screwfix, Toolstation, or any drainage supplier. Once you own it, you can pre-test every section of drainage in the build before the inspector arrives, and any leaks become trench-side fixes rather than re-inspection failures.

What Building Control actually tests

The drainage inspection in England and Wales is governed by Approved Document H of the Building Regulations and references BS EN 1610 (Construction and testing of drains and sewers). Approved Document H (paragraph 2.59) says gravity drains should be tested for watertightness after laying, including any concrete haunching or surround and the backfilling, using an air test or a water test. Many inspectors also watch a test at the open-trench visit, before backfilling.

The standard air test is a low-pressure test:

Test stagePressureTest durationAllowable drop
Your own air test, trench open110mm water gauge held about 5 minutes to settle, then 100mm (~10mbar)7 minutesLoss not exceeding 25mm water gauge
Formal air test after backfilling (AD H 2.60)110mm water gauge held about 5 minutes to settle, then 100mm7 minutesLoss not exceeding 25mm water gauge
Water test (alternative, AD H 2.61)At least 1m of water at the highest invert, no more than 5m above the lowest; left about an hour to condition30 minutes, topped up to within 100mm of the test levelLoss not exceeding 0.15 litres per m² of internal surface (pipes only), 0.20 with manholes

The air test is the standard for short residential runs because it's quick to perform and a single test covers a long length of pipe in one operation. The water test is the alternative; a sealed pipe filled with water to at least 1m above its highest invert is left to condition, then allowed to lose water at a defined maximum rate.

For homeowner extension work, you'll almost certainly be tested with the air test. Knowing the pass criterion (no more than 25mm loss over 7 minutes from a 100mm starting pressure, after the pipe has settled at 110mm for about 5 minutes) tells you what your own pre-test needs to demonstrate.

Tip

Buy a kit with a U-tube manometer rather than a digital gauge. The U-tube reads pressure in millimetres of water column directly, which is the unit the Building Regulations specify. Digital gauges in mbar require conversion (10mbar = 100mm water column) and the conversion adds a step where homeowners get confused.

How to run an air test before the inspector arrives

The procedure is the same one the BCO will run, just done a day earlier with the trench still accessible.

  1. Identify the test section

    A drainage run typically runs from the soil stack at the house to the connection to the existing soil pipe or new manhole. The test section is usually one continuous run between two access points (rodding eyes, inspection chambers, or open ends).

  2. Seal the lower end with the drain bung

    Insert the inflatable or expanding 110mm drain bung into the lower end of the test section. Inflate or expand it to seal against the pipe wall. The bung must hold without slipping under test pressure.

  3. Connect the pump and manometer to the upper end

    Attach the flexible hose from the pump to the upper end of the section. The U-tube manometer connects to the same line so it reads the pressure inside the pipe.

  4. Pump up to 110mm water column

    Pump air into the section until the manometer reads 110mm water column (about 11mbar on a digital gauge). Stop pumping at 110mm.

  5. Wait about five minutes for stabilisation

    Pressure inside the pipe rises slightly when air is pumped in (the air heats up under compression) and then stabilises as the air cools to ambient temperature. Approved Document H holds the pipe at 110mm for about five minutes before the test. Then let the pressure down to exactly 100mm.

  6. Watch the gauge for seven minutes

    Start a timer. Watch the manometer for seven minutes without further pumping. The reading should not drop more than 25mm water column over the seven-minute period.

  7. If the test passes, you're ready for the BCO

    A drop of no more than 25mm in 7 minutes is a pass. Take a photo of the manometer reading at the start and end of the test as evidence. Pack the kit; you've already done the inspection.

  8. If the test fails, find and fix the leak

    A drop greater than 25mm means a leak. Common causes: a poorly seated rubber gasket, an unsupported pipe joint that's pulled slightly apart, a hairline crack from a pipe being dropped before laying, or the bung itself not sealing. Pour a soapy water solution along visible joints; bubbles indicate the leak. Re-seal the joint and retest.

For the post-backfill test (after the trench is filled and the concrete oversite is poured), the kit setup is the same. The leak is harder to find because the joints are buried, which is exactly why the pre-backfill test matters: catching leaks while the trench is open is twenty minutes of work; catching them after concrete is poured is half a day of breaking out and re-pouring.

Pre-test versus the BCO visit: the value calculation

A re-inspection visit from a Local Authority Building Control team costs typically 100 to 200 pounds in 2026, plus the time delay (usually one to two weeks for a re-booking). Private registered building control approvers charge similar re-inspection fees.

A failed inspection also affects the groundworker's payment milestone. Most homeowner-managed builds pay groundworks at completion of drainage sign-off; a failure delays that payment by a week or more, which annoys the groundworker and can sour the working relationship.

Compare those costs against 40 pounds for the test kit. Even if the kit is used once and never again, it pays for itself the first time it catches a leak before the BCO visit. The Pareto reality is that most drainage runs pass on first inspection, so the kit catches a problem in maybe one in three uses; even at that rate the cost-benefit is overwhelmingly positive.

The same kit also lets you test the existing house drainage if you're tying into it, which catches age-related leaks in the existing run that would otherwise become your problem after the new work is signed off.

What to buy

The market for homeowner-grade drain test kits is small and the brands are interchangeable.

TierApprox priceModelsWhat you get
Budget£25-40Drain Master Air Test Kit (Screwfix), Floplast 110mm test bung + manual pump separately, generic eBay air test kits110mm bung, hand pump, basic gauge. Functional but the manometer may be a single rigid plastic tube rather than U-tube
Mid-range£45-70Polypipe Air Test Kit (Toolstation), Drainage Sales Direct kitsInflatable bung with screw clamp, U-tube manometer, robust hand pump, carry bag
Trade£90-150Lanes Group test kit, Camlin Air Test Kit, Pearpoint MK20Calibrated digital gauge, multiple bung sizes (100mm, 110mm, 150mm), professional carry case
Hire£25-35/weekBrandon Hire, HSS, Speedy HireTrade-grade kit with calibration; no purchase commitment

For a single homeowner kit purchase: any of the budget or mid-range options work. The Drain Master kit at Screwfix (around 40 pounds) is the most accessible and the one most homeowners on UK forums report buying. The Polypipe kit at Toolstation is the next step up at around 55 pounds and includes the U-tube manometer, which is easier to read.

The hire option is worth considering if you only need the kit for a single drainage run and don't expect to use it again. 30 pounds for a week from any major hire shop, with a properly calibrated trade-grade kit included.

Warning

Drain bungs under pressure are stored energy. A bung that comes loose under air pressure can fly out of the pipe at significant force. Stand to one side of the pipe end during the test, never directly in line with the bung. The pressures involved (100mm water column is approximately 0.01 bar) are low, but a bung released suddenly can still cause injury at close range. The risk is greater on water tests where the pressures and energies are higher.

Where you'll use it

The drain test kit comes out at the drainage stage of the build:

Once the drainage is signed off, the kit goes back in the cupboard. The next time you'll need it is if you ever extend or alter drainage on this or any other property.

When to use other tests

The air test is the standard. Two adjacent tests have specific use cases.

Water test: Building control accepts it as the alternative, and it is the usual second check when an air test fails, because air tests are sensitive to a slightly leaking bung or a temperature change. A water test seals the lower end with the bung, fills the pipe with water from the upper end (at least 1m above the highest invert), leaves it about an hour to condition, then measures how much water has to be added over 30 minutes to keep the level up (Approved Document H paragraph 2.61). Slower to perform but less easily upset than an air test.

Smoke test: Specialist test using non-toxic smoke pumped into the drainage system to find leaks visually. Used by drainage surveyors when a test fails but the leak location isn't obvious. Approved Document H (paragraph 1.38) does not recommend smoke testing for PVC-U pipes. Not a homeowner-grade test; commission a specialist if the air test repeatedly fails and the leak can't be found.

CCTV survey: A camera on a flexible rod inspects the inside of the drain run. Used for condition surveys of existing drainage, particularly when buying a property with old clay pipework. Around 150 to 300 pounds for a residential CCTV survey from a local drainage company.

Common mistakes

Skipping the pre-test entirely. The single biggest mistake. The 40 pound kit pays for itself the first time it catches a leak. Almost every homeowner-managed build that fails drainage inspection would have passed if a pre-test had been done.

Starting the timed test above 100mm water column. The pipe settles at 110mm, but the seven-minute test starts from 100mm. Starting the clock higher means you can falsely pass the test (more pressure margin to fall through), and pumping well past 110mm risks blowing the bung out.

Not waiting for stabilisation before the test starts. In the first few minutes after pumping, the air inside the pipe cools and contracts. Pressure drops naturally and looks like a leak. Hold at 110mm for about five minutes, bring it to 100mm, then start the seven-minute test clock.

Testing immediately after laying without time for joints to settle. Rubber gasket joints sometimes need a few hours to fully seat against the pipe wall. Test the day after laying rather than the same hour, particularly if joints have been disturbed during backfilling.

Reusing a damaged bung. The bung's seal must be perfect. A bung that has been dragged across rough concrete or stored in a damp toolbox can develop small surface defects that leak under test pressure. Inspect the bung surface before each use; replace if any cuts or compression damage are visible.

Forgetting the post-backfill retest. Approved Document H (paragraph 2.59) sets the watertightness test after laying and backfilling. A test with the trench open is for your benefit (and often what the inspector watches at the drainage visit); the test after backfilling is the one the guidance asks for. Both matter.

Where to buy Drain Test Kit

Check current prices from UK suppliers.

These are affiliate links: if you buy through them we may earn a small commission, at no extra cost to you. Learn more.

Doing the whole extension yourself?

Get the free budget spreadsheet. Every cost category for a UK kitchen extension, with contingency and cost per m² worked out for you.

Get the free spreadsheet

Want the full step-by-step guide, planning through to completion? See the Access Pass

More in this category

Related reference pages

HygrometerBS-mandated moisture testing tool for measuring screed relative humidity before flooring is laid. The hygrometer box method (insulated box sealed to the screed surface for 72 hours, then RH measured inside) is the only BS 8203/BS 8204-compliant approach. Concrete moisture meters are not a substitute for the box test under any major UK flooring warranty.Moisture MeterA handheld instrument for rapidly screening surface moisture in plaster, timber, masonry, and screed. Pin-type meters measure electrical resistance between two probes pushed into the material; pinless (radio-frequency) meters scan to 20-40mm depth without surface penetration. Used to check plaster dryness before painting, timber moisture content before finishing, and quick triage before a formal hygrometer box test. Not a substitute for BS 8203/BS 8204 hygrometer box testing before resilient floor coverings.Crack MonitorA calibrated device affixed across a crack to track whether it is stable or progressing over time. Provides a permanent dated record of crack movement. Used to monitor cracks at the old/new junction on extensions during the defects liability period, and to evidence stability in party-wall disputes.DehumidifierElectric appliance that removes moisture from the air, used to speed up plaster drying in new extensions and to condition a build before second-fix joinery is installed. Compressor models work well in warm conditions; desiccant models are more effective in cold, unheated spaces. Can be purchased or hired (£44-100/week).

General guidance for homeowners in England (and Wales where we say so), not professional advice. Every site is different: check anything that affects your build with a qualified professional, your local council or building control. Terms