Skip to main content
buildwiz.uk

Flooring Underlay: Types, UFH Compatibility, and What Goes Under Each Floor Finish

Flooring underlay: foam vs rubber vs cork, tog ratings for UFH, which underlay goes under laminate or LVT, and why the wrong type voids your floor warranty.

By Ian

Project managed a £182k Oxfordshire kitchen extension

A floor finisher installs engineered oak on a UFH screed, with a standard 3.5mm foam underlay underneath because it was what the builder had on site. Eighteen months later the homeowner reports cold spots on the floor and rising energy bills. The UFH system is working; the floor temperature sensors show the screed is reaching the set point. The problem is the underlay acting as an insulating blanket between the warm screed and the room above. The thermal resistance of that foam underlay is high enough to make the UFH economically inefficient, and it breaks the floor manufacturer's fitting instructions for use over UFH.

Underlay is the one flooring component where the wrong choice cannot be fixed without lifting the whole floor.

What flooring underlay is and why it matters

Flooring underlay is a thin layer of compressible or cushioning material laid between the subfloor (usually concrete screed or timber boarding) and a floating floor covering. It serves four purposes:

  • Acoustic dampening: reduces impact sound (footfall noise) transmitted through the floor structure to the rooms below. Relevant for multi-storey houses and conversion projects.
  • Minor subfloor irregularities: bridges small surface undulations in the screed or boarding so the floor covering is not supported on high spots only.
  • Thermal insulation: adds a small amount of thermal resistance between the floor covering and the room. On a well-insulated concrete slab this has little practical effect. Over UFH it has a large and potentially damaging effect.
  • Moisture barrier: some underlays incorporate a polythene vapour layer on the underside that reduces moisture vapour transfer from a green screed into the floor covering above. This is not a substitute for a damp-proof membrane at slab level.

The choice of underlay is governed primarily by the floor covering it will sit under, the substrate it sits on, and whether there is underfloor heating in the screed.

UFH compatibility: the tog limit

If the floor has a wet underfloor heating system in the screed, the combined thermal resistance of the floor covering and the underlay must stay below the limit specified by the UFH designer and the floor and UFH manufacturers.

0.15 m²K/W combined tog limit

The thermal resistance limit (floor covering plus underlay combined) commonly specified for UFH compatibility. Equivalent to approximately 1.5 tog. Exceeding it reduces UFH efficiency and may void the floor or UFH manufacturer's warranty.

Thermal resistance in floor products is usually expressed in m²K/W (sometimes loosely called "tog" in retailers, where 1 tog = 0.1 m²K/W). The limit of 0.15 m²K/W covers both the floor covering and the underlay together. A typical LVT floor covering has a thermal resistance around 0.01–0.03 m²K/W. A typical 3.5mm foam underlay has a thermal resistance of 0.08–0.12 m²K/W. Together they sit close to, and can reach, the 0.15 limit, which is why a thin UFH-rated underlay is used instead. A thicker underlay (5mm foam) pushes the combined value over the threshold.

For engineered wood, the floor covering itself has a higher thermal resistance (0.10–0.12 m²K/W for typical 18mm boards). Adding any underlay of meaningful thickness pushes the total over the limit. For UFH under engineered wood, use a very thin (1–1.5mm) thermally conductive underlay only if the UFH designer has confirmed the combined value is acceptable.

Warning

Using a standard foam underlay over a UFH screed is one of the most common flooring mistakes on extension projects. Check the combined thermal resistance of your chosen floor covering and underlay against the UFH designer's specification before buying. The consequence of exceeding the limit is not just reduced comfort: it can void the floor or UFH warranty.

Types of underlay and what they suit

Foam underlay (polyethylene foam)

The most common type. Closed-cell PE foam, typically 2–5mm thick, sold in rolls. Available in standard and premium grades. Some grades incorporate a thin vapour layer on one face. It is inexpensive, easy to fit (cut with scissors or a knife), and gives good performance under laminate and floating engineered wood on non-UFH substrates.

Not suitable over UFH unless specified to a very thin profile and confirmed thermally compliant.

Rubber crumb underlay

Made from recycled car tyres. Higher density and more dimensionally stable under load than foam. Good acoustic performance. Suits heavy foot traffic and is often specified under luxury engineered wood and floating floors in commercial applications. More expensive than foam. Check manufacturer's thermal resistance figures if used over UFH.

Cork underlay

A natural product with good acoustic and thermal properties. 2–3mm thickness. Compressible enough to absorb minor subfloor variation. Suits floating floors on timber substrates where acoustic performance is important. Check thermal resistance against the UFH limit if applicable.

LVT-specific underlay

LVT (luxury vinyl tile) and sheet vinyl are thin, dimensionally stable, and respond badly to subfloor irregularities that compress unevenly under the product. LVT-specific underlays are typically 1–1.5mm, very dense, and designed to support the thin flooring without allowing it to flex over imperfections. Some LVT is designed to be laid without underlay (glue-down or click-lock direct on a prepared screed). Check the manufacturer's fitting instructions before specifying any underlay for LVT.

For LVT over underfloor heating, use only an underlay approved for the exact floor. Some floors have integrated backing or need no separate underlay. Check the floor and heating manufacturers' combined thermal-resistance limit; there is no universal underlay-only limit of 0.03 m²K/W.

Acoustic underlay (specialist)

For refurbishments and conversions where Part E acoustic separation is a performance target, specialist acoustic underlays with high mass and low resonant frequency are available. These are not general-use products but are specified by acoustic engineers for particular constructions. They are more expensive and thicker than standard underlays.

Four main underlay types suit different floor coverings and substrates. Over UFH, thickness and thermal resistance govern the choice, not acoustic performance.

Which underlay goes under which floor

Floor coveringStandard underlay typeUFH: use this insteadNotes
Laminate3–5mm PE foam with vapour layer1.5–2mm UFH-rated foamCheck combined tog < 0.15 m²K/W
Floating engineered wood2–3mm foam or cork1–1.5mm thermally conductive underlay or noneUFH: always confirm with UFH designer
Click-lock LVT1.5mm LVT acoustic underlay1.5mm UFH-rated LVT underlayDo not use standard foam under LVT over UFH
Glue-down LVTNone: direct to screedNone requiredScreed must be flat to BS 8204 SR1 or the LVT maker's tolerance
Carpet8–10mm foam or rubberLow-tog UFH carpet underlayKeep carpet + underlay within the UFH maker's limit (often 1.5–2.5 tog)

Fitting underlay: practical points

Underlay is laid loose before the floor covering goes down. The fitting process is straightforward but the common errors matter.

Direction: follow the underlay and floor manufacturers' instructions for roll direction, stagger and seam placement. Do not assume all products require perpendicular laying.

Joints: butt the underlay sheets tightly together at the edges without overlapping. An overlapping underlay joint creates a ridge that the floor covering will follow, producing a visible line on the finished floor surface. Tape butted joints with general-purpose tape to stop them shifting during installation. On a concrete subfloor the vapour layer must be continuous: lap and tape the film lip of an underlay with an integrated vapour layer, or with a plain underlay lay a separate polythene sheet (typically 0.2mm, 200mm taped laps) first.

Walls: the underlay runs up to the wall but not up the wall face. The gap at the perimeter of a floating floor (required for expansion) sits between the floor edge and the skirting board, not under the underlay.

Subfloor prep: the subfloor must be flat to the tolerances the floor manufacturer specifies before any underlay goes down. Underlay does not bridge bumps or fill hollows in any meaningful way. A 3mm foam underlay will conform to a 3mm high spot in the screed and transmit it to the floor covering above, often visibly. Grind or fill the screed to the required tolerance first.

Vapour layer orientation: fit the product with the specified face upwards and seal the joints as instructed. Foil or polythene position varies by product; moisture control depends on a continuous correctly detailed barrier, not a universal silver-side-down rule.

Reading the manufacturer's fitting instructions

Every floor manufacturer specifies the underlay type that is acceptable under their product, and many void the product warranty if an unspecified underlay is used. Before buying underlay, find the floor manufacturer's fitting instructions and confirm the following:

  • Maximum underlay thickness permitted
  • Whether an integrated vapour layer is required (if laying on concrete)
  • Thermal resistance limit (if over UFH)
  • Whether the floor can be laid without underlay in some circumstances (glue-down LVT)

This step takes five minutes and prevents the most common cause of flooring failures that result in a voided warranty.

Moisture and vapour considerations

On a concrete screed in a new extension, the screed will still be releasing moisture vapour for months after pouring. A DPM under the slab controls rising ground moisture. The vapour layer on many foam underlays provides limited additional protection against vapour rising from a warm screed in the interim period.

For engineered wood, the hygrometer box test (BS 8201 Annex A for wood flooring) must confirm the screed is below the manufacturer's specified RH threshold (typically 75% RH, or 65% RH over underfloor heating) before the floor is installed. An underlay with a vapour barrier does not eliminate the requirement for the screed to be dry. It delays but does not prevent moisture-related damage if the floor is installed too early.

What it costs

Underlay is priced per m², with rolls typically 7–10m² for standard residential use or 15–20m² per roll for larger projects.

TypeThicknessPrice per m²Typical roll size
Standard PE foam (with vapour layer)3.5mmCheck current supplier price10m²
Premium foam acoustic5mmCheck current supplier price10m²
Rubber crumb5–8mmCheck current supplier price6m²
Cork sheet2–3mmCheck current supplier price5–7m²
LVT / UFH specialist1–1.5mmCheck current supplier price10m²

Where to buy Flooring Underlay

Check current prices from UK suppliers.

These are affiliate links: if you buy through them we may earn a small commission, at no extra cost to you. Learn more.

Underlay for carpet

Carpet underlay follows different rules from the types covered above. A separate guide would cover carpet underlay in full, but the key points relevant to an extension project are:

  • Standard carpet underlay (8–12mm foam or rubber) produces a combined thermal resistance with the carpet that typically exceeds the UFH limit. Carpet can go over UFH only with a low-tog underlay, keeping the combined value within the UFH maker's limit (often quoted as 1.5 to 2.5 tog, with the lower figure for heat pumps).
  • For non-UFH rooms, carpet underlay thickness is a matter of comfort and budget: thicker underlay makes carpet feel more luxurious underfoot and extends carpet life by reducing flex at the backing.
  • Rubber crumb underlay is preferred in high-traffic hallways and stairs because it does not compress permanently under repeated point loading the way foam does.

Part E acoustic compliance

In conversions and multi-occupancy residential buildings, separating floors between dwellings must meet an impact sound insulation level under Building Regulations Part E. Approved Document E Table 0.1a sets L'nT,w of 64 dB or less for flats formed by a material change of use (62 dB for new-build). Meeting this with a floating floor typically requires:

  • An independent floating screed or platform deck, not just an underlay
  • A high-mass, low-frequency resonant underlay as part of the build-up
  • Testing by an acoustic engineer before the floor is signed off

A standard flooring underlay does not achieve Part E compliance on its own in any construction likely to be encountered on a domestic extension. If Part E compliance is a requirement of the project, involve an acoustic specialist early to specify the floor build-up. This applies where a project creates a separate dwelling above or below another, such as a house split into flats. A loft conversion within one house only needs its new internal floor to meet the Part E airborne standard (Rw 40 dB), which comes from the floor build-up, not the underlay.

The cost difference between a standard foam underlay and a UFH-rated specialist underlay is small (typically one to three pounds per m²) against the cost of re-laying a floor because the underlay was incompatible. On a 25m² kitchen extension floor, that difference is 25 to 75 pounds. On an engineered oak floor costing several thousand pounds in material and labour, the risk-adjusted saving is clear.

What to buy for a 25m² kitchen extension floor

For a typical single-storey kitchen extension with a UFH screed:

  1. Confirm the floor covering type and the UFH designer's thermal resistance limit.
  2. Read the floor covering manufacturer's installation instructions to confirm approved underlay types and thicknesses.
  3. For LVT or laminate with UFH: choose a 1.5mm UFH-rated underlay with a combined tog value confirmed below 0.15 m²K/W.
  4. For engineered wood with UFH: consult the UFH designer. Many manufacturers specify either no underlay, or a purpose-designed 1mm thermally conductive product.
  5. Order sufficient rolls for the area, with 5–10% waste allowance for cutting.

For a room with no UFH (a first-floor extension or a room above ground on a suspended floor), a 3.5mm PE foam underlay is the standard choice for laminate or engineered wood (with an integrated vapour layer only on a concrete subfloor, not on timber boards). It is widely stocked and performs reliably in that application. The guidance above is specific to UFH situations because that is where the wrong choice causes the most costly failures, but for standard non-UFH floors the key decision is simply to match the underlay to the floor covering type and to confirm it carries a vapour layer for concrete subfloors.

Where this fits in your build

This is one step in a bigger build. Pick up the sequence around it.

Pricing up this job?

The Flooring Cost Estimator gives you a quick estimate for this part of the work. Free, no email needed.

Open the calculator

Budgeting the whole extension? Get the free spreadsheet with every cost category and contingency worked out, or follow the full step-by-step guide with the Access Pass.

More in this category

Related reference pages

Laminate FlooringA budget floor covering with a printed wood/stone image over HDF. Not recommended for kitchens due to moisture sensitivity at joints. Also impedes UFH efficiency. Frequently confused with LVT or engineered wood by homeowners.Luxury Vinyl TileA tile or plank format floor covering with a durable wear layer. Three installation formats: click, glue-down, and looselay. Increasingly popular for kitchen extensions: warm underfoot, water-resistant, and compatible with UFH. Glue-down format preferred in south-facing extensions with large glazing for thermal stability.LVT AdhesiveSpecialist adhesive for glue-down LVT. Two types: wet-set (hard-set, permanent bond) and pressure-sensitive (PS, allows repositioning). In south-facing extensions with large glazing, wet-set adhesive is required to prevent LVT shrinkage from direct sunlight. Not interchangeable with tile adhesive.Porcelain Floor TilesThe most durable and UFH-compatible floor finish for kitchen extensions. Large-format tiles (60x60cm) are a common choice for open-plan extensions. Requires flexible (S1 class minimum) tile adhesive and a decoupling membrane over UFH screed to prevent cracking from thermal expansion.Tile Levelling SystemPlastic clips and wedges used to hold adjacent tiles at the same height during adhesive set, eliminating lippage. Essential for large-format tiles (60×60cm and above).Transition StripA metal, wood, or plastic profile that covers the join between two different floor finishes or accommodates a height difference at the threshold. Must be planned before flooring is laid, not after. Critical at the junction between extension floor and existing house floor.

General guidance for homeowners in England (and Wales where we say so), not professional advice. Every site is different: check anything that affects your build with a qualified professional, your local council or building control. Terms